1 Function as Modbus-TCP server

Modbus-TCP, ASCII protocol • VEGAMET 391/624/625, VEGASCAN 693, PLICSRADIO C62

30768-EN-130701

Register address in

Modicon

Temporary memory of VEGAMET/PLICSRADIO

(1 word = 2 byte)

30004

PC/DCS output 2: Status

30005

PC/DCS output 3: Measured value

30006

PC/DCS output 3: Status

30007

PC/DCS output 4: Measured value

30008

PC/DCS output 4: Status

30009

PC/DCS output 5: Measured value

30010

PC/DCS output 5: Status

30011

PC/DCS output 6: Measured value

30012

PC/DCS output 6: Status

Register address in

Modicon

Temporary memory of VEGASCAN (1 word =

2 byte)

30001

PC/DCS output 1: Measured value

30002

PC/DCS output 1: Status

30003

PC/DCS output 2: Measured value

30004

PC/DCS output 2: Status

30005

PC/DCS output 3: Measured value

30006

PC/DCS output 3: Status

30007

PC/DCS output 4: Measured value

30008

PC/DCS output 4: Status

30009

PC/DCS output 5: Measured value

30010

PC/DCS output 5: Status

30011

PC/DCS output 6: Measured value

30012

PC/DCS output 6: Status

30057

PC/DCS output 29: Measured value

30058

PC/DCS output 29: Status

30059

PC/DCS output 30: Measured value

30060

PC/DCS output 30: Status

As an alternative, register address 40001 is also available as start

address (function code 03).

The actual measured values are transmitted as signed data compris-

ing two octets. This means that the value range encompasses max.

+32768 to -32767. In addition to the measured value, the status of the

measured value is delivered in a second register word.

Format of the PC/DCS