VEGA Modbus-TCP, ASCII protocol User Manual

Page 5

Advertising
background image

5

1 Function as Modbus-TCP server

Modbus-TCP, ASCII protocol • VEGAMET 391/624/625, VEGASCAN 693, PLICSRADIO C62

30768-EN-130701

Example of the data of a PC/DCS output

Measured value

Status

Register addr. 30001

Register addr. 30002

High-Byte/Low-Byte

High-Byte/Low-Byte

The status describes the condition of the associated measured value.

The content of the measured value is only valid if the corresponding

status has the value zero. If there is a status value unequal zero, the

status value and the corresponding value in the measured value field

must be taken into account in a detailed failure diagnosis. The follow-

ing chart explains the possible faults.

Status

Measured

value

Meaning

0x00

0xXXXX

Valid measured value

0xXX

0x8000

An error number is transmitted in the status

corresponding to the error codes Exx (e.g. 29

= E29 = Simulation).

0xXX

0x00XX

An error number which corresponds to the er-

ror codes Exx is transmitted in the status and

in the measured value. Must be configured

via DTM.

Note:

When transmitting the PC/DCS value in Modbus-TCP protocol

(measured value filing as 2 byte short), the decimal point itself is not

transmitted; the value -0.5 bar is transmitted as -50. If a data format

was selected that allows values outside the value range to appear, a

limit is set at the highest value of the value range.
Example: Percent was selected as "Reference value " and #.### as

"Data format ". With this setting, the value 100 % would be transmit-

ted as 100000, which is outside the valid range of max. +32767. This

means that a limit will be imposed and 32767 transmitted instead.

To avoid this, "Data format " #.## should be chosen so that the value

100 % is transmitted as 10000.
Note:

On the switching inputs of PLICSRADIO C62 (measurement loops

4 … 6) the values 0 (switch open) and 100 (switch closed) are trans-

mitted as measured values; the units are discarded.

The switching conditions of the relay are transferred as bit information.

The following equivalencies apply to the switching relays:

0 = Switching status Off

1 = Switching status On

The following equivalencies apply to the fail safe relay:

0 = Failure message Off, relay switching condition On

1 = Failure message Off, relay switching condition Off

The following chart shows the addressing of the temporary memory

via Modbus.

Filing of the relay values

Advertising