26

2 ASCII protocol

Modbus-TCP, ASCII protocol • VEGAMET 391/624/625, VEGASCAN 693, PLICSRADIO C62

30768-EN-130701

Enquiry:

$001
Answer:

=001# 824.6 #kg

$ Block enquiry

All assigned PC/DCS values in the instrument are delivered as reply

to the block enquiry. The measured value is transmitted with 11 deci-

mal places as floating point and with unit.

Number of bytes

Character

Identifier

1

$

End identification

1

CR

Identifier: "$" (1 character)

End identification: Carriage Return CR (1 sign)

Total length of the telegram: 2 characters
"N"-times repetition of the following telegram

(N=total number of assigned PC/DCS outputs)

Number of bytes

Character

T1

1

=

DCS no.

3

001 … 030

T2

1

#

Value

11

-824.6

T3

1

#

Unit

0 … n

xxx

End identification

1

CR

T1: "=" (1 character)

DCS no.: No. of the PC/DCS output as 3-digit decimal number

T2: "#" (1 character)

Value: Numerical value of the PC/DCS output or with interferred

measured value the error code "Exxx"

Formatting of the value:

Character

Meaning

1

"- ": Minus with negative numbers
" ": Space with positive numbers

2 … 12

11-digit number with comma or error code

T3: "#" (1 character)

Unit: Unit as text (0 … n unit)

End identification: Carriage Return CR (1 sign)

Total length of the telegram: N*(18 characters+Unit character)