3 filing of measured value as 4 byte float – VEGA Modbus-TCP, ASCII protocol User Manual

Page 6

Advertising
background image

6

1 Function as Modbus-TCP server

Modbus-TCP, ASCII protocol • VEGAMET 391/624/625, VEGASCAN 693, PLICSRADIO C62

30768-EN-130701

Register ad-

dress in

Modicon

Temporary memory of VE-

GAMET/PLICSRADIO (1 bit)

Temporary memory of VE-

GAMET 391 (1 Bit)

10001

Fail safe relay

Fail safe LED

10002

Relay 1

Relay 1

10003

Relay 2

Relay 2

10004

Relay 3

Relay 3

10005

----

Relay 4

10006

----

Relay 5

10007

----

Relay 6

1.3 Filing of measured value as 4 Byte Float

The filing of measured values in the temporary memory is always

sorted according to PC/DCS output number. The following chart

shows the addressing of the temporary memory via Modbus. The

values are accessed via FC 3 and 4. The status information is also

transmitted as float value. 8 byte are needed for one output, corre-

sponding to 4 registers.
Information:

Note: A float value comprises 2 registers, i.e. a total of 4 bytes!

Register address in

Modicon

Temporary memory of VEGAMET/PLICSRADIO

(2 words = 4 byte)

31001

PC/DCS output 1: Measured value

31003

PC/DCS output 1: Status

31005

PC/DCS output 2: Measured value

31007

PC/DCS output 2: Status

31009

PC/DCS output 3: Measured value

31011

PC/DCS output 3: Status

31013

PC/DCS output 4: Measured value

31015

PC/DCS output 4: Status

31017

PC/DCS output 5: Measured value

31019

PC/DCS output 5: Status

31021

PC/DCS output 6: Measured value

31023

PC/DCS output 6: Status

Register address in

Modicon

Temporary memory of VEGASCAN (2 words =

4 byte)

31001

PC/DCS output 1: Measured value

31003

PC/DCS output 1: Status

31005

PC/DCS output 2: Measured value

31007

PC/DCS output 2: Status

31009

PC/DCS output 3: Measured value

Advertising