9 measured value enquiry with command – VEGA Modbus-TCP, ASCII protocol User Manual

Page 25

Advertising
background image

25

2 ASCII protocol

Modbus-TCP, ASCII protocol • VEGAMET 391/624/625, VEGASCAN 693, PLICSRADIO C62

30768-EN-130701

=001# 000673#%

=002# 00824#kg

=003#-000673#m

2.9 Measured value enquiry with command $

$ individual enquiry

The PC/DCS value stated in the enquiry is delivered as reply to the

individual enquiry. The measured value is transmitted with 11 decimal

places as floating point and with unit.

Number of bytes

Character

Identifier

1

$

Begin

1 … 3

001 … 030 or 1 … 30

End identification

1

CR

Identifier: "$" (1 character)

Start: No. of the requested PC/DCS output (1 … 3 characters)

End identification: Carriage Return CR (1 sign)

Total length of the telegram: 3 … 5 characters

Number of bytes

Character

T1

1

=

DCS no.

3

001 … 030

T2

1

#

Value

11

-824.6

T3

1

#

Unit

0 … n

xxx

End identification

1

CR

T1: "=" (1 character)

DCS no.: No. of the PC/DCS output as 3-digit decimal number

T2: "#" (1 character)

Value: Numerical value of the PC/DCS output or with interferred

measured value the error code "Exxx"

Formatting of the value:

Character

Meaning

1

"- ": Minus with negative numbers
" ": Space with positive numbers

2 … 12

11-digit number with comma or error code

T3: "#" (1 character)

Unit: Unit as text (0 … n unit)

End identification: Carriage Return CR (1 sign)

Total length of the telegram: 18 characters+Unit character

Enquiry of the control

system

Reply from the signal

conditioning instrument