8 measured value enquiry with command – VEGA Modbus-TCP, ASCII protocol User Manual

Page 20

Advertising
background image

20

2 ASCII protocol

Modbus-TCP, ASCII protocol • VEGAMET 391/624/625, VEGASCAN 693, PLICSRADIO C62

30768-EN-130701

(End-Start+1)-times repetition of the following telegram

Number of bytes

Character

T1

1

=

DCS no.

3

001 … 030

T2

1

#

Value

5 … 6

-000673

T3

1

%

End identification

1

CR

T1: "=" (1 character)

DCS no.: No. of the PC/DCS output as 3-digit decimal number

T2: "#" (1 character)

Value: Numerical value of the PC/DCS output or with interferred

measured value the text "FAULT"

Formatting of the value:

Character

Meaning

1

"- ": Minus with negative numbers
" ": Space with positive numbers

2 … 7

6-digit number after the decimal point

T3: "%" (1 character)

End identification: Carriage Return CR (1 sign)

Total length of the telegram: (End-Start+1)*14
Note:

The % sign is a separator, not the unit %
Enquiry:

&001-003
Answer:

=001# 000673%

=002# 008246%

=003#-000673%

2.8 Measured value enquiry with command?

? individual enquiry

The PC/DCS value stated in the enquiry is delivered as reply to the

individual enquiry. The measured value is transmitted with six decimal

places without decimal point and with unit.

Number of bytes

Character

Identifier

1

?

Begin

1 … 3

001 … 030 or 1 … 30

End identification

1

CR

Identifier: "?" (1 character)

Reply from the signal

conditioning instrument

Example:

Enquiry of the control

system