VEGA Modbus-TCP, ASCII protocol User Manual

Page 19

Advertising
background image

19

2 ASCII protocol

Modbus-TCP, ASCII protocol • VEGAMET 391/624/625, VEGASCAN 693, PLICSRADIO C62

30768-EN-130701

Number of bytes

Character

T3

1

%

End identification

1

CR

T1: "=" (1 character)

DCS no.: No. of the PC/DCS output as 3-digit decimal number

T2: "#" (1 character)

Value: Numerical value of the PC/DCS output or with interferred

measured value the text "FAULT"

Formatting of the value:

Character

Meaning

1

"- ": Minus with negative numbers
" ": Space with positive numbers

2 … 7

6-digit number after the decimal point

T3: "%" (1 character)

End identification: Carriage Return CR (1 sign)

Total length of the telegram: Quantity*14 signs
Note:

The % sign is a separator, not the unit %
Enquiry:

&001L003
Answer:

=001#-000673%

=002# 008246%

=003#-000673%

& Block enquiry with range

The range stated in the enquiry with PC/DCS values is delivered as

reply to the range enquiry. The measured value is transmitted with six

decimal places without decimal point and unit.

Number of bytes

Character

Identifier

1

&

Begin

1 … 3

001 … 030 or 1 … 30

Separator

1

-

End

1 … 3

001 … 030 or 1 … 30

End identification

1

CR

Identifier: "&" (1 character)

Start: Start no. of the requested PC/DCS output (1 … 3 charac-

ters)

Separator: "-" (1 sign)

End: End no. of the requested PC/DCS output (1 … 3 characters)

End identification: Carriage Return CR (1 sign)

Total length of the telegram: 5 … 9 characters

Example:

Enquiry of the control

system

Advertising