VEGA Modbus-TCP, ASCII protocol User Manual

Page 8

Advertising
background image

8

1 Function as Modbus-TCP server

Modbus-TCP, ASCII protocol • VEGAMET 391/624/625, VEGASCAN 693, PLICSRADIO C62

30768-EN-130701

Status

Measured

value

Meaning

<> 0

0

An error number is transmitted in the status

corresponding to the error codes Exx (e.g. 29

= E29 = Simulation).

<> 0

XX0XX

An error number which corresponds to the er-

ror codes Exx is transmitted in the status and

in the measured value. Must be configured

via DTM.

The switching conditions of the relay are transferred as bit information.

The following equivalencies apply to the switching relays:

0 = Switching status Off

1 = Switching status On

The following equivalencies apply to the fail safe relay:

0 = Failure message Off, relay switching condition On

1 = Failure message Off, relay switching condition Off

The following chart shows the addressing of the temporary memory

via Modbus.

Register ad-

dress in

Modicon

Temporary memory of VE-

GAMET/PLICSRADIO (1 bit)

Temporary memory of VE-

GAMET 391 (1 Bit)

10001

Fail safe relay

Fail safe LED

10002

Relay 1

Relay 1

10003

Relay 2

Relay 2

10004

Relay 3

Relay 3

10005

----

Relay 4

10006

----

Relay 5

10007

----

Relay 6

As an alternative, register address 00001 is also available as start

address.

Filing of the relay values