40

6 Set up with the display and adjustment module

MINITRAC 31 • Profibus PA

43836-EN-131119

Note:

Make sure that some products have a self-radiation. This is for ex-

ample the case with oil or potash salt lye. Therefore the tube must be

filled to determine the background radiation.
For this purpose, the MINITRAC 31 measures the natural background

radiation and sets the pulse rate to zero.
In the future, the pulse rate from this background radiation will be

automatically deducted from the total pulse rate. This means: only

the component of the pulse rate originating from the source will be

displayed.
The source container must be closed for this setting (OFF).

In this menu item you can select the units of the process value and

the temperature.

In this menu item you can enter the measuring range (min. and max.

process value) of the sensor.
These settings influence the current output of the sensor.

Enter in the menu window "Max. process value" the max. density

value, for example in "g/cm

3

". This corresponds to an output current

of 20 mA.

Enter in the menu window "Min. process value" the min. density value,

for example in "g/cm

3

". This corresponds to an output current of 4 mA.

In this menu item you can enter the inside diameter of the tube or the

radiated length (L).
This setting influences the accuracy of the sensor.

Setup - Units

Setup - Adjustment

Setup - Inside diameter