2 connect – VEGA VEGAPULS 62 (≥ 2.0.0 - ≥ 4.0.0) Profibus PA Approval according to LPR radio standard User Manual

Page 26

Advertising
background image

connected to ground potential or to another cable screen. The cable
screens to the power supply unit and to the next distributor must be
connected to each other and also connected to ground potential via a
ceramic capacitor (e.g. 1 nF, 1500 V). Low-frequency potential
equalisation currents are thus suppressed, but the protective effect
against high frequency interference signals remains.

5

.2 Connect

The voltage supply and signal output are connected via the spring-
loaded terminals in the housing.

The connection to the indicating and adjustment module or to the
interface adapter is carried out via contact pins in the housing.

Proceed as follows:

1

Unscrew the housing cover

2

If an indicating and adjustment module is installed, remove it by
turning it slightly to the left.

3

Loosen compression nut of the cable entry

4

Remove approx. 10 cm (4 in) of the cable mantle, strip approx.
1 cm (0.4 in) of insulation from the ends of the individual wires

5

Insert the cable into the sensor through the cable entry

Fig. 18: Connection steps 5 and 6

6

Insert the wire ends into the terminals according to the wiring plan

Connection technology

Connection procedure

26

VEGAPULS

62 • Approval according to LPR radio standard

5 Connecting to the bus system

41720

-EN

-120301

Advertising