VEGA VEGAPULS 62 (≥ 2.0.0 - ≥ 4.0.0) Profibus PA Approval according to LPR radio standard User Manual

Page 71

Advertising
background image

-

Double chamber housing

l

1 x cable entry M20 x 1.5 (cable: ø 5 … 9 mm),
1 x blind stopper M20 x 1.5; 1 x blind stopper
M

16 x 1.5 or optional

7)

1 x plug M12 x 1 for

external indicating and adjustment unit

or:

l

1 x closing cap ½ NPT, 1 x blind stopper
½ NPT

, 1 x blind stopper M16 x 1.5 or

optionally

8)

1 x plug M12 x 1 for external

indicating and adjustment unit

or:

l

1 x plug (depending on the version), 1 x blind
stopper M20 x 1.5; 1 x blind stopper M16 x 1.5
or optionally

9)

1 x plug M12 x 1 for external

indicating and adjustment unit

Spring-loaded terminals for wire cross-section

-

Massive wire, cord

0.2 … 2.5 mm² (AWG 24 … 14)

-

Stranded wire with end sleeve

0.2 … 1.5 mm² (AWG 24 … 16)

Electromechanical data - version IP 66/IP 68 (1 bar)

Cable entry

-

Single chamber housing

1 x IP 68 cable gland M20 x 1.5; 1 x blind stopper
M

20 x 1.5

-

Double chamber housing

1 x IP 68 cable gland M20 x 1.5; 1 x blind stopper
M

20 x 1.5; 1 x blind stopper M16 x 1.5

Connection cable

-

Wire cross-section

0.5 mm² (AWG 20)

-

Wire resistance

<

0.036 Ω/m

-

Tensile strength

<

1200 N (270 lbf)

-

Standard length

5 m (16.4 ft)

-

Max. length

180 m (590.6 ft)

-

Min. bending radius

25 mm (0.984 in) with 25 °C (77 °F)

-

Diameter approx.

8 mm (0.315 in)

-

Colour - standard PE

Black

-

Colour - standard PUR

Blue

-

Colour - Ex-version

Blue

Indicating and adjustment module

Voltage supply and data transmission

through the sensor

Indication

LC display in dot matrix

Measured value indication

7)

Only with Ex d version

8)

Only with Ex d version

9)

Only with Ex d version

VEGAPULS

62 • Approval according to LPR radio standard

71

11 Supplement

41720

-

EN

-120301

Advertising