VEGA VEGAPULS 62 (≥ 2.0.0 - ≥ 4.0.0) Profibus PA Approval according to LPR radio standard User Manual

Page 78

Advertising
background image

Status code

Description according
to Profibus standard

Possible cause

0 x 00

bad - non-specific

Flash-Update active

0 x 04

bad - configuration error

l Adjustment error
l Configuration error with PV-Scale (PV-Span too

small)

l Unit irregularity
l Error in the linearization table

0 x 0C

bad - sensor failure

l Hardware error
l Converter error
l Leakage pulse error
l Trigger error

0 x 10

bad - sensor failure

l Measured value generation error
l Temperature measurement error

0 x 1f

bad - out of service cons-
tant

"O

ut of Service" mode switched on

0 x 44

uncertain - last unstable
value

Failsafe replacement value (Failsafe-Mode = "Last
value" and already valid measured value since swit-
ching on)

0 x 48

uncertain substitute set

l Switch on simulation
l Failsafe replacement value (Failsafe-Mode = "Fsafe

value")

0 x 4c

uncertain - initial value

Failsafe replacement value (Failsafe-Mode = "Last valid
value" and no valid measured value since switching on)

0 x 51

uncertain - sensor; con-
version not accurate - low
limited

Sensor value < lower limit

0 x 52

uncertain - sensor; con-
version not accurate - high
limited

Sensor value > upper limit

0 x 80

good (non-cascade) - OK

OK

0 x 84

good (non-cascade) - ac-
tive block alarm

Static revision (FB, TB) changed (10 sec. active, after
the parameter of the static category has been written)

0 x 89

good (non-cascade) - ac-
tive advisory alarm - low
limited

Lo-Alarm

0 x 8a

good (non-cascade) - ac-
tive advisory alarm - high
limited

Hi-Alarm

0 x 8d

good (non-cascade) - ac-
tive critical alarm - low
limited

Lo-Lo-Alarm

78

VEGAPULS

62 • Approval according to LPR radio standard

11 Supplement

41720

-EN

-120301