VEGA VEGAPULS 62 (≥ 2.0.0 - ≥ 4.0.0) Profibus PA Approval according to LPR radio standard User Manual

Page 67

Advertising
background image

Accuracy (according to DIN EN 60770-1)

Process reference conditions according to DIN EN 61298-1

-

Temperature

+

18 … +30 °C (+64 … +86 °F)

-

Relative humidity

45 … 75 %

-

Air pressure

860 … 1060 mbar/86 … 106 kPa (12.5 … 15.4 psig)

Installation reference conditions

-

Min. distance to installations

>

200 mm (7.874 in)

-

Reflector

Corner reflector

-

False reflections

Largest false echo 20 dB smaller than the useful
echo

Deviation with liquids

See following diagrams

0,5 m (1.6 ft)

10 mm (0.394 in)

2 mm (0.079 in)

- 2 mm (- 0.079 in)

- 10 mm (- 0.394 in)

0

1 2

3

Fig. 48: Deviation under reference conditions

1

Reference plane

2

Antenna edge

3

Recommended measuring range

Reproducibility

≤ ±

1 mm

Deviation with bulk solids

The values depend to a great extent on the
application. Binding specifications are thus not
possible.

Variables influencing measurement accuracy
Temperature drift - Digital output

±

3 mm/10 K relating to the max. measuring range

or max. 10 mm

Additional deviation through strong, high
frequency electromagnetic fields acc. to EN
61326

< ±

50 mm

VEGAPULS

62 • Approval according to LPR radio standard

67

11 Supplement

41720

-

EN

-120301

Advertising