Input variable
Measured variable
The measured quantity is the distance between
process fitting of the sensor and product surface.
The reference plane is the seal surface on the
hexagon or the lower side of the flange.
3
4
2
1
Fig. 47: Data of the input variable
1
Reference plane
2
Measured variable, max. measuring range
3
Antenna length
4
Useful measuring range
Max. measuring range
35 m (114.83 ft)
Output variable
Output signal
digital output signal, format according to IEEE-754
Sensor address
126 (default setting)
Damping (63 % of the input variable)
0 … 999 s, adjustable
Profibus PA profile
3.02
Number of FBs with AI (function blocks with
analogue input)
3
Default values
-
1. FB
PV
-
2. FB
SV
1
-
3. FB
SV
2
Current value
-
Non-Ex and Ex ia instrument
10 mA, ±0.5 mA
-
Ex d instruments
16 mA, ±0.5 mA
Resolution, digital
<
1 mm (0.039 in)