6 Set up with the display and adjustment module

VEGAFLEX 81 • HART - integrated accumulator

44640-EN-130430

Caution:

Note the following, if the respective sensor is used as part of an over-

fill protection system according to WHG:
If a linearization curve is selected, the measuring signal is no longer

linear to the level. This must be taken into consideration by the user,

particularly when setting the switching point on the limit signal indica-

tor.
In the following, you have to enter the values for your vessel, for

example the vessel height and the socket correction.
For non-linear vessel forms, enter the vessel height und the socket

correction.
For the vessel height, you have to enter the total height of the vessel.
For the socket correction you have to enter the height of the socket

above the upper edge of the vessel. If the socket is lower than the up-

per edge of the vessel, this value can also be negative.

+ h

D

- h

Fig. 20: Vessel height und socket correction value
D Vessel height

+h Positive socket correction value

-h Negative socket correction value