11 Supplement

VEGAFLEX 81 • HART - integrated accumulator

44640-EN-130430

Ʋ Cable probes

ε

r

≥ 1.6

Ʋ Rod probes

ε

r

≥ 1.6

2

4

5

3

2

4

5

3

1

1

Fig. 37: Measuring ranges - VEGAFLEX 81
1 Reference plane

2 Probe length L

3 Measuring range (default setting refers to the measuring range in water)

4 Upper dead band (see diagrams under Accuracy - grey section)

5 Lower dead band (see diagrams under Accuracy - grey section)

Accuracy (according to DIN EN 60770-1)
Process reference conditions according to DIN EN 61298-1

Ʋ Temperature

+18 … +30 °C (+64 … +86 °F)

Ʋ Relative humidity

45 … 75 %

Ʋ Air pressure

+860 … +1060 mbar/+86 … +106 kPa

(+12.5 … +15.4 psig)

Installation reference conditions

Ʋ Min. distance to installations

> 500 mm (19.69 in)

Ʋ Vessel

metallic, ø 1 m (3.281 ft), centric installation, process

fitting flush with the vessel ceiling

Ʋ Medium

Water/Oil (dielectric constant ~2.0)

1)

Ʋ Installation

Probe end does not touch the vessel bottom

Sensor parameter adjustment

No gating out of false signals carried out

Typical deviation - Interface measure-

ment

± 5 mm (0.197 in)

1)

With interface measurement = 2.0