6 Set up with the display and adjustment module

VEGAFLEX 81 • HART - integrated accumulator

44640-EN-130430

This menu item displays the peak values of the electronics tempera-

ture as well as the dielectric constant.

In another window you can carry out a reset of the two peak values

separately.

The menu item "Echo curve" shows the signal strength of the echoes

over the measuring range in V. The signal strength enables an evalua-

tion of the quality of the measurement.

With the following functions you can zoom part sections of the echo

curve.

"X-Zoom": Zoom function for the meas. distance

"Y-Zoom": 1, 2, 5 and 10x signal magnification in "V"

"Unzoom": Reset the presentation to the nominal measuring range

with single magnification

In this menu item you can simulate measured values via the current

output. This allows the signal path to be tested, e.g. via downstream

indicating instruments or the input card of the control system.

Select the requested simulation size and adjust the requested value.

Caution:

During simulation, the simulated value is outputted as 4 … 20 mA cur-

rent value and digital HART signal.
Push the [ESC] key to deactivate the simulation.

Diagnostics - Echo curve

Diagnosis - Simulation