3 Product description
VEGABAR 83 • Profibus PA
45037-EN-131107
4
3
2
1
Fig. 4: Configuration of the METEC
®
measuring cell
1 Process diaphragm
2 Isolating liquid
3 FeNi adapter
4 CERTEC
®
measuring cell
The measuring cell design depends on the selected pressure type.
Relative pressure: the measuring cell is open to atmosphere. The
ambient pressure is detected in the measuring cell and compensated.
It thus has no influence on the measured value.
Absolute pressure: the measuring cell is evacuated and encapsu-
lated. The ambient pressure is not compensated and does hence
influence the measured value.
Relative pressure, climate-compensated: the measuring cell is
evacuated and encapsulated. The ambient pressure is detected
through a reference sensor in the electronics and compensated. It
thus has no influence on the measured value.
The measuring system is completely welded and hence sealed
against the process. The sealing of the process fitting against the
process is carried out by a seal provided on site.
3.3 Packaging, transport and storage
Your instrument was protected by packaging during transport. Its
capacity to handle normal loads during transport is assured by a test
based on ISO 4180.
The packaging of standard instruments consists of environment-
friendly, recyclable cardboard. For special versions, PE foam or PE
foil is also used. Dispose of the packaging material via specialised
recycling companies.
Transport must be carried out in due consideration of the notes on the
transport packaging. Nonobservance of these instructions can cause
damage to the device.