Dynamic behaviour output
Run-up time approx.

10 s

Dynamic characteristics, depending on medium, temperature and, if applicable, chemical seal

90 %

100 %

10 %

t

t

T

A

t

t

S

2

1

Fig. 38: Behaviour in case of sudden change of the process variable. t

T

: dead time; t

A

: rise time; t

S

: jump response

time
1 Process variable

2 Output signal

Dead time

< 45 ms

Rise time

> 35 ms (10 … 90 %)

Step response time

> 80 ms (ti: 0 s, 10 … 90 %)

Damping (63 % of the input variable)

0 … 999 s, adjustable

Reference conditions and actuating variables (according to DIN EN 60770-1)
Reference conditions according to DIN EN 61298-1

Ʋ Temperature

+18 … +30 °C (+64 … +86 °F)

Ʋ Relative humidity

45 … 75 %

Ʋ Air pressure

860 … 1060 mbar/86 … 106 kPa (12.5 … 15.4 psi)

Determination of characteristics

Limit point adjustment according to IEC 61298-2

Characterstic curve

Linear

Reference installation position

upright, diaphragm points downward

Influence of the installation position

Ʋ Piezoresistive/strain gauge measur-

ing cell

depending on the process fitting and the chemical seal

Ʋ METEC

®

measuring cell

< 5 mbar/0.5 kPa (0.07 psig)

Deviation (according to IEC 60770)
Specifications refer to the set span. Turn down (TD) is the ratio: nominal measuring range/set span.

Accuracy class

Non-linearity, hysteresis and re-

peatability with TD 1 : 1 up to 5 : 1

Non-linearity, hysteresis and re-

peatability with 5 : 1

0.075 %

< 0.075 %

< 0.015 % x TD

0.1 %

< 0.1 %

< 0.02 % x TD