VEGA VEGABAR 83 Profibus PA - Operating Instructions User Manual

Page 43

Advertising
background image

43

6 Set up with the display and adjustment module

VEGABAR 83 • Profibus PA

45037-EN-131107

In delivery status, the PIN is "0000".

In this menu item, you adjust the internal clock of the sensor. There is

no adjustment to summer/winter time.

With a reset, certain parameter adjustments carried out by the user

are reset.

The following reset functions are available:
Delivery status: Restoring the parameter settings at the time of

shipment from the factory incl. the order-specific settings. A user-pro-

grammable linearization curve as well as the measured value memory

will be deleted.
Basic settings: Resetting the parameter settings incl. special

parameters to the default values of the respective instrument. A pro-

grammed linearization curve as well as the measured value memory

is deleted.
The following table shows the default values of the instrument. De-

pending on the instrument version or application, all menu items may

not be available or some may be differently assigned:

Reset - Setup

Menu item

Parameter

Default value

Sensor address

126

Measurement

loop name

Sensor

Application

Application pro-

cess pressure
Application level

No reset

Slave for elec-

tronic differential

pressure

No reset

Additional adjustments -

Date Time

Additional adjustments

- Reset