40

6 Set up with the display and adjustment module

VEGABAR 83 • Profibus PA

45037-EN-131107

A linearization is necessary for all vessels in which the vessel volume

does not increase linearly with the level - e.g. a horizontal cylindri-

cal or spherical tank - and the indication or output of the volume is

required. Corresponding linearization curves are preprogrammed for

these vessels. They represent the correlation between the level per-

centage and vessel volume. The linearization applies to the measured

value indication and the current output.

Caution:

Note the following, if the respective sensor is used as part of an over-

fill protection system according to WHG:
If a linearization curve is selected, the measuring signal is no longer

necessarily linear to the filling height. This must be considered by the

user especially when adjusting the switching point on the limit signal

transmitter.

In menu item "Scaling" you define the scaling variable and the scaling

unit for the level value on the display, e.g. volume in l.

In menu item "Scaling (2)" you define the scaling format on the display

and the scaling of the measured level value for 0 % and 100 %.

In the menu item "Lock/unlock adjustment", you can protect the

sensor parameters against unauthorized modification. The PIN is

activated/deactivated permanently.
The following adjustment functions are possible without entering the

PIN:

Select menu items and show data

Read data from the sensor into the display and adjustment mod-

ule.

Caution:

With active PIN, adjustment via PACTware/DTM as well as other

systems is also blocked.

Setup - Linearization

Setup - Scaling (1)

Setup - Scaling (2)

Lock/release setup - Ad-

justment