3.2.6.2 005 – 022

Du/dt filter at motor supply is needed if

-

Motors are not made for inverter use

-

Inverter is not mounted on the crane

-

Number of motors is greater than 4

-

Total motor cable length is over 200m (660ft)

Power class Platthaus du/dt filter

Length (mm)

Width (mm)

Height (mm)

Weight (kg)

ID

002 – 003

ULC-910-920

100

110

180

1.2

52306553

004 – 005

ULC-914-931

125

110

200

3

52306554

007 – 018

ULC-918-951

155

125

225

7

52306555

022

ULC-923-927

190

135

260

12

52306556

3.3 EMC compatible grounding

3.3.1 Construction connections

All metal construction parts of the cubicle must be electrically connected to each other using largest
possible surface area. Paint to paint connection must not be used.

3.3.2 Cable connections

Control cables and power cables should be separated and routed separately for eliminating noise
coupling. The distance between braking resistor cables and the other cables should be kept as large as
possible. The distance between the resistor cables should be kept as short as possible to prevent the
antenna behavior. Cable lengths should be kept as short as possible to minimize coupling capacitances
and inductances.

#

Du/dt filter should be installed as close as possible to inverter.

#

All control cables must be placed as far as possible from the motor and braking resistor cables.

#

Please take care of the necessary cooling/heating to ensure that the ambient temperature of
inverter is within –10

°C to +50 °C if it is installed in a harsh environment.

!

If EMC / Noise problems occur during your installation, please follow the EMC plan or
contact the manufacturer.