Check minimum speed from the crane calculations. Minimum speed is not allowed to be under

nominal slip

ed

syncronspe

frequency

nom

speed

nom

ed

syncronspe

S

n

.

*

)

.

(

=

5.4.2 Autotuning

Before Autotuning,

-

Check that there is no load on the crane.

-

Set P1.1.1. “Password” = 2156

-

Set P1.2.2 “Motor selection” = 1 “Free Travel”

-

Set Motor nameplate values P1.2.1, P1.2.4.1- P1.2.4.3

-

(if value of P1.2.4.3 “Nom Flux Curr” is not available, set to value 0,00. Parameter P1.2.4.3 will be used if it’s
value differs from 0.00. Otherwise P1.2.4.5 “Motor Cos Phi” value will be used.)

-

Set Motor nameplate values P1.2.4.5 “Motor Cos Phi” as it will be used when value of P1.2.4.3 is 0.00.

- Check

motor

connections



-

Go to parameter P1.2.4.6

-

Push Start over 2 seconds to start
Autotuning

-

Autotuning can be terminated pushing
Stop-button.

-

Autotuning values will be accepted
automatically if Autotuning did not fail
or was not terminated.


-

When parameter P1.2.4.6 has value
“3”, Autotuning has been done
successfully.


-

If parameter P1.2.4.6. has value “2”,
Autotuning has failed or has been
stopped. Check motor parameters and
motor connection.

STOP

I/O term

I/O term

I/O term

I/O term

I/O term

> 2s

START

The explanations on Autotuning parameter P1.2.4.6 is as follows:

Parameter number

Parameter name

Description

P1.2.4.6

Autotuning

0 Autotuning has not been done
1 Autotuning in progress
2 Autotuning has been failed
3 Autotuning values has been accepted
4 Autotuning values has been modified

Autotuning will set open loop U/f-curve, RsVoltageDrop, torque boost and current limit parameters
automatically.

Parameter number

Parameter name

P1.2.5.1 Zero

Freq

Volt

P1.2.5.2 U/f

Mid

Volt

P1.2.5.3 U/f

Mid

Freq

P1.2.5.4

Torque boost => on

P1.2.5.7 Rs

Voltage

Drop

P1.2.4.4 Current

Limit