6.2.1 Reverse Plugging

When opposite drive command is active while the inverter is operating, the deceleration/acceleration
ramp can be shorter than the normal ramp. Reverse plugging function is “on” if the driving frequency >
30% of the “Max Freq” (not the “Motor Nom Freq”). Reverse plugging function goes “off state” in opposite
direction to original direction when driving frequency > 95% of reference frequency.
The value can be set between 50 to 100%. 100% corresponds that the ramp is the same as the normal
ramp. 50% corresponds that the ramp is a half of the normal ramp. The default value is 80%.

6.2.2 Relay output

Inverter has one programmable relay output (ROA1) and one relay output for brake control (ROD1).
Relay output functions for ROA1 are listed below.

Par value

Name

Description

0

Not Used

1

Fault

Relay is activated when fault is on.

2

Brake Control

External brake ON/OFF-control. Default value in relay output ROD1
(K7 control).

3

Run

Relay is activated when current is fed to motor.

4

Ready

Relay is activated when Drive is ready to operate.

5

Ready Inverted

Relay is activated when Drive is not ready to operate.

6

Fan

Relay is activated when DC-link voltage is above braking chopper operating level - 70V.
Relay is closed for a minimum of 300s.

7

Emergency Stop

Relay is activated in case of F1 Overcurrent, F2 Overvoltage or F3 Earth Fault. Relay is
deactivated when the power is switched off.

8

Reverse Plugging

Relay is activated when direction requested is different than direction of actual frequency.

9

At Speed

Relay is activated when ramp generator output has reached speed reference request.

10

S2 Active

Relay is activated when motor actual speed direction is S2.

11

Temp 1

Relay contact is activated when temperature is 20

°C (68F) or below. Relay is inactivate when

temperature is 23

°C (73F) or above.

12

Temp 2

Relay contact is activated when temperature is 40

°C (104F) or above. Relay is inactivate

when temperature is 37

°C (98F) or below.