ASTAT-CD Plus Service Instructions

13

Carefully release the terminal connectors
from pins (Figure 2) and remove the
connectors (with wiring) from the starter.
Carefully pull the terminal connectors
straight off the ASTAT-CD Plus starter.

Step 3. Remove the plastic cover by using a flat-head

screwdriver to depress and release the plastic
tab on each side of the plastic cover (see
Figure 2 in Sizes F, G, H and I section).

To replace the Logic Board

Important: Always handle boards by
edges and do not distort parts on board.

Step 4. The top printed circuit board is the Logic

Board.

Ribbon cable

Screw

Logic Board

Ribbon cable

Figure 3. Logic Board parts location

Step 5. To remove Logic Board, unplug the two

ribbon cables from the Logic Board.

Step 6. Remove the 4 corner screws holding the

Logic Board to the standoffs below the Logic
Board. Remove the Logic Board (Figure 3).

Step 7. Reassemble Logic Board to the starter. With

the display on the Logic Board at the upper
left corner, place the board on the standoffs
and attach the Logic Board in the reverse
order as listed in Steps 6 and 5 above. Make
sure the ribbon cable at the bottom of the
ASTAT is fully seated on both circuit boards
and that the ribbon cable will not interfere
with or touch the cover.

Sizes N, Q, R or S

Cover removal

NOTE: POWER MUST BE REMOVED

BEFORE SERVICING.

Screws

Figure 1. Cover screw locations

Step 1. Remove the front steel cover by removing the

4 Phillips screws (Figure 1).

Terminal connector

Cover

Figure 2. Terminal removal

Step 2. Remove the two 12- point plug-in terminal

connectors by inserting a flat- head
screwdriver between the terminal connectors
and that ASTAT-CD Plus cover (Figure 2).

Do not remove wiring from
terminal connectors.

Advertising