4

To replace Protection Board

NOTE: POWER MUST BE REMOVED
BEFORE SERVICING.

Current
transformers

6- point Terminal
Board

MOVs

Protection Board

Figure 9. Protection Board

Step 13. Remove the cover, Logic Board and Power

Supply Board using steps 1 - 10.

Step 14. Reposition red MOVs as shown. Raise MOVs

and twist so that Protection Board can be
removed over the MOVs (Figure 10).

MOV

Power
Supply
and Logic
Board
assembly

Figure 10. MOV positioning

Step 15. Disconnect the 4 leads from the 2 current

transformers and remove the jumper on pins
1 and 2 on the 6 -point Terminal Board (TB),
located at the top right edge of the Protection
Board. Identify these lead locations to assure
the same connections are made to the 6-
point Terminal Board on the new Protection
Board (Figure 11).

Current
transformer leads

6- point Terminal
Board

Small screwdriver

Figure 11. Removing wires from Terminal

Board

Step 16. Loosen the 6 screws holding the Protection

Board to the main bus bars. Remove the
Protection Board from the ASTAT-CD Plus
(Figure 12).

Remove 6 screws holding Protection Board

Figure 12. Remove screws