ASTAT-CD Plus Service Instructions

3

Step 8. Remove the 4 screws holding the Power

Supply Board to the black plastic housing
(Figure 6).

Screws to remove

Figure 6. Removing screws holding Power

Supply Board

Step 9.

Lower the top of the Power Supply Board to
view the yellow and blue gate leads to the
SCRs (Figure 7).

NOTE: Check the blue and yellow gate wires
for a number marking before removing
these wires. Each gate wire must have a
number marking correlating to the terminal
numbers on the Power Supply Board (1
through 12) to facilitate reassembly.

Gate leads

Protection Board

Bottom of Power Supply Board

Gate terminal board

Figure 7. Gate leads, Protection and

Power Supply Boards

Step 10. Remove the blue and yellow gate wires from

the small 4- point gate Terminal Boards, 1 on
the component side and 2 on the solder side
of the Power Supply Board, with a small
screwdriver.

These wires must be reconnected to the new
Power Supply Board at the proper numbered
terminals for proper operation of the starter.

Remove the Power Supply Board. Remove
the hex standoffs, nuts and washers from the
Power Supply Board for use on the
replacement board.

Step 11. Reassemble the standoffs to the new Power

Supply Board. Reconnect the gate wires.
Reference Figure 8 for gate lead connections.

Step 12. Reassemble the Logic Board, cover and

terminal connectors using Steps 5 - 6.

Figure 8. Gate lead connections

Y = yellow wire.

B = blue wire.

SCR lead pairs are to be twisted to reduce EMI

(not shown in sketch).