ASTAT-CD Plus Service Instructions

31

Symptom or Error & (Error Code) Possible Cause

Measures to be taken

Phase A, B, C loss (Ex19) No input / output phases

Check power wire harness for 1L1, 3L2, 5L3, 2T1, 4T2

(Ex20)

and 6T3

(Ex21) Defective thyristor or ribbon wire

Verify gate and cathode wire harness.

harness loose or defective

Verify thyristors

Stalled rotor (Ex22) Equipment detected stalled motor rotor

Restart equipment and check for an appreciable

loss in motor speed at any time

Internal error (Ex23) Micro-controller malfunction

Check IC1 and IC8 are correctly inserted in their

sockets. Check for noise on control voltage

power or line

Long start time (Ex25) Current limit condition present more

Increase current limit and / or

than 2 x ta sec. or 240 sec.

acceleration ramp time

(ta = acceleration ramp time)

Long slow speed time (Ex26) Equipment has been in slow speed

Reduce time slow speed is engaged

mode more than 120 sec.

Lock-out (Ex27) The time between startings is less that

Check if settings are correct

the adjusted in parameter "LKxx"

This protection may be disabled

Undervoltage (Ex28) The line voltage exceeds of limit set

Check if settings are correct.

Overvoltage (Ex29) in parameters "UVxx" or "OVxx"

This protection may be disabled

Undercurrent (Ex30) The motor current exceeds of limit set

Check if settings are correct.

Overcurrent (Ex31)

in parameters "UCxx" or "OCxx"

This protection may be disabled

Retry (Ex32)

The retry feature could not re-start the

Check last message "e1xx" and correct.

motor after a fault

Be sure that retry settings are correct as well