Step 15. Reassemble the standoffs to the new Power

Supply Board. Reconnect the gate wires to
the Power Supply Board (terminals 1 to 12)
and reinstall the 4 screws which hold the
Power Supply Board to the black plastic
housing. Refer to (Figure 7) for gate lead
connections.

Step 16. Reassemble the Logic Board, cover and

terminal connectors using steps 7-10.

Figure 7. Gate lead connections

Y = yellow wire. B = blue wire.

SCR lead pairs are to be twisted to

reduce EMI (not shown in sketch).

To replace the Protection Board.

NOTE: POWER MUST BE REMOVED
BEFORE SERVICING.

Step 17. Remove the Cover, steps 1-3, and remove the

(Logic and Power Supply Board assembly) by
removing the 4 screws holding the Power
Supply Board to the black housing. If a
yellow/green wire is connected to the bottom

of the Power Supply Board, it must be
disconnected. Lower the Logic and Power
Supply Board assembly (Figure 8). Remove the
blue and yellow gate wires per steps 13 and 14.

6-point Terminal Board

Protection Board

6-wire connectors

Power Supply and
Logic Board Assembly

Figure 8. Board location

Step 18. Label the 6 push-on wire connectors with the

numbers printed on the P.C. Board (U1, V1,
W1, U2, V2, W2). Remove 6 push-on wire
connectors from the Protection Board
(Figure 9). Note the location of these
terminals for reassembly.

Mounting screw

6-point Terminal Board

Protection Board

Wire connectors

Figure 9. Remove wire connectors