GE Industrial Solutions WattStation Pedestal EVSE Charger Operation and Maintenance User Manual

Page 55

Advertising
background image

WattStation™ EV Charger User Manual

5555

GE Energy

©2012 GE Company All Rights Reserved




It is possible with ungrounded power sources that unintentional “parasitic” leakage paths to ground
will be sufficient for the ground monitor circuit to be satisfied at times, so this fault may only
sporadically appear.

The WattStation Pedestal is designed to operate correctly from either centrally grounded
(e.g. L1 – N – L2) or end-grounded (e.g. Line – Neutral) power sources. O

Onn eenndd--ggrroouunnddeedd ppoow

weerr

ssoouurrcceess m

maakkee ssuurree tthhee ““hhoott”” m

maaiinn iiss ccoonnnneecctteedd ttoo tthhee LL11 iinnppuutt aanndd tthhee nneeuuttrraall m

maaiinn

iiss ccoonnnneecctteedd ttoo tthhee LL22 iinnppuutt..

C

Cooddee 221155 –– C

Chhaarrggee C

Coonnttrroolllleerr ccoom

mm

muunniiccaattiioonn ffaauulltt

This alarm indicates that the charge controller has stopped communicating with the communication
controller. This should be a transient condition which should automatically clear. If not, try cycling AC
power until the condition clears. If persistent the charge controller and/or the communication
controller will need to be replaced.

Advertising