Arc Vault™ Protection System

DEH-41483 Rev. 3

Receiving, Handling and Storage

6

© 2011 General Electric All Rights Reserved

CAUTION

Remove all cartons, containers and any other

miscellaneous packaging and packing material from

inside the switchgear sections before energizing any

internal heaters. To prevent fire, remove any plastic or

polyethylene shrouding from the switchgear sections

before energizing any internal heaters.

3. If dampness or condensation may be encountered in

the storage location, heaters must be placed inside

the switchgear sections to prevent moisture damage.

Approximately 250 watts of heat in each section is

required. On outdoor switchgear equipment, this

may be accomplished by making a temporary power

supply connection to the heaters already installed in

the equipment.

CAUTION

If the space heaters are to be temporarily energized

from external source, it is important to remove the

fuses on the secondary side of the control power

transformer. This precaution is to prevent a feed back

of higher voltage to other portions of the equipment

through the CPT primary.