DEH-41483 Rev. 3

Arc Vault™ Protection System

Initial Test and Activation

© 2011 General Electric All Rights Reserved

31

SECTION 8. INITIAL TEST AND ACTIVATION

WARNING

Before starting the test and activation procedure,

make sure to be wearing personal protective

equipment (PPE) and follow local work rules.

IMPORTANT: For AC system with UPS installed, make sure

UPS is powered up and charged before continuing.

MAKING ARC VAULT READY TO TEST

1. Locate Activation Switch. See Figure 8-1.

2. Verify all indicator lights are working properly by

rotating Activation Switch counter clockwise and hold.

3. Release Activation switch knob to OFF position.

Indicator lights will go off.

4. Place Arc Vault on horizontal rails after sliding rails

forward from cassette.

5. With device resting on all four rail pins, push device into

cassette until it hits the racking cam.

6. Slide horizontal rails in all the way.

7. Close compartment door and rotate door latch 90

degrees to the engaged position.

8. Depress red "Push To Discharge" button. Arc Vault

device must be in the discharged state before racking

in.

9. Follow procedure for racking the device to the test

position. See Installation Procedures on page 23.

10. When secondary disconnects engage, the red

Capacitor Status discharge light turns on. You now

have control power provided. The Red device status

light at the top will also turn on.

11. Verify the device is in the test position by using the

alignment markers on the top of the device.

12. Remove Racking tool. Device will not charge unless

racking tool is removed.

13. Manually charge the device by depressing the "Push to

Charge" button. Device is charging, indicated by the

yellow Capacitor Status light.

14. Green light above Push to Discharge button will

illuminate when fully charged. Approximate charge

time is 90 seconds.

IMPORTANT: If the system has been in the discharged

mode, or not powered, for more than a year in a warm

ambient environment, it may take longer than 2

minutes for the system to complete self-test and

indicate Fully Charged. Once the system is Fully

Charged, leave it charged for 30 minutes.

 

15. Green Arc Vault device status indicator light will

illuminate when fully charged.

16. Device is now ready to test.

CAUTION

System is not yet active at this point, as indicated by

system status light.

.