Caution, Warning – GE Industrial Solutions Arc Vault Protection System User Manual

Page 30

Advertising
background image

Arc Vault™ Protection System

DEH-41483 Rev. 3

Equipment Installation

22

© 2011 General Electric All Rights Reserved

Where the cables enter the section, they can be lashed to

optional cable supports at the rear of the cable

compartment as required.

Mechanical cable terminals are normally included with the

switchgear (compression terminals are supplied when

ordered) and are mounted at the ends of the breaker

runbacks in the cable compartment. Carefully follow the

cable manufacturer's recommendations for installation of

cable.

Install the cables in the proper path to the terminals, using

temporary lashing if required. Cut the cables to the proper

length. Strip the insulation to the desired dimension, being

careful not to damage any strands.

For copper cables, coat the wires with GE lubricating grease

D6A15A2, insert the cables into the terminals, and tighten

per torque values in Table A-2 in Appendix A.

For aluminum cables, wire brush the wire strands

thoroughly. Immediately after wire brushing, coat the cable

strands with a quality oxide inhibiting compound such as

Penetrox A. Insert exposed wires into the terminals and

tighten the set screws in accordance with values shown in

the torque Table A-2 in Appendix A.

CAUTION

The torque values shown in the table are for dry

threads only. Do not grease or otherwise lubricate the

threads on the cable terminals as this will permit

over-tightening of the screw and possible damage to

the terminal or cable.

This should result in the oozing of compound material from

between individual strands. Wipe off any excess compound.

Bolt the cable terminal connectors to the ends of the bars in

the cable compartment. A non-oxidizing grease, such as GE

lubricating grease D6A15A2 furnished with each

equipment, should be used at these connection surfaces.

The bolts should be tightened in accordance with values

shown in the torque Table A-2 in Appendix A.

Lash the cables securely to the cable support, if present, to

take their weight off the runbacks and to brace them

against short circuit forces in the event of a fault.

WARNING

Risk of shock. The equipment must be completely de-

energized before installing or removing the arc fault

device. Failure to do so may result in death or serious

injury.

Figure 4-8 Typical cable lashing

The cable supports in Figure 4-8 can be optionally ordered

from the factory. The following instructions for cable

lashing should be used as a guide. Run and bend the main

cable in a most convenient orientation, making sure the

main cable has been located directly up against any cable

braces (if present) before it connects to the main cable

terminals.

Using a 3/8 inch diameter continuous nylon rope or

equivalent (minimum 2000 pounds tensile strength) at 6

inches from the main cable terminals, make five revolutions

around the "A" and "B" phase main cables, making sure the

rope does not overlap. Make five revolutions around the "B"

and "C" phase main cables. With the remaining rope, wrap

around the main cable lashing between the "B" and "C"

phase and the cable brace (if present) with a minimum of 5

revolutions getting as much revolutions as possible

between the phases. Continue wrapping between the "A"

and "B" phase around the main cable lashing and the cable

brace (if present) with a minimum of 5 revolutions getting as

much revolutions as possible between the phases. Securely

tie off the remaining rope. Repeat this lashing at every 6-

inch interval.

Relays and Control Devices

Remove all blocking on relays and devices as shown in the

instructions accompanying the devices.

Nylon rope – 3/8
inch (9.5 mm)
diameter.
Minimum of 5
wraps

6 inches
(152 mm)

Advertising