DEH-41483 Rev. 3

Arc Vault™ Protection System

Description

© 2011 General Electric All Rights Reserved

11

Figure 3-6 Arc Vault primary disconnect shutters in closed position

1. Cassette Walls

2. Shutters (retractable barrier)

3. Shutter Operating lever

4. Racking mechanism insertion port

The shutters are closed when the Arc Vault is in the

DISCONNECT Position. As the Arc Vault is racked from the

DISCONNECT Position to the TEST Position the shutters

remain fully closed. As the device is racked from the TEST

Position to the CONNECTED Position, the shutters open

allowing the device to connect to the primary disconnects.

The cassette racking arm slots engage fixed racking

anchor pins on the sides of the Arc Vault. As the racking

arms are rotated by operation of the racking crank, the Arc

Vault is pulled into the compartment, and locked in its final

connected position.

Note that extra items shown in Figure 3-6, (such as

secondary disconnects and shutters) are optional and may

appear in any compartment or not be included at all,

depending on the equipment specified.