Arc Vault™ Protection System

Troubleshooting

© 2011 General Electric All Rights Reserved

39

SECTION 12.

TROUBLESHOOTING

The following chart is a simple trouble shooting checklist

only. If the suggested solution does not succeed, or if the

information is insufficient to solve the problem, please

phone GE Engineering field services at 888-GE4-SERV (888-

434-7378) or GE Resolve at 888-437-3765.

WARNING

Most of the problems may result in partial or no

protection.

Problem

Possible

cause

Solution

1

Racking access door screw

not rotating

Push to charge button is

depressed on device

Depress push to discharge

button

2

Push to charge button does

not depress fully.

Device is not in test or

connect position.

Rack device to test or connect

position.

3

Red light on device and

instrument tray is off after

discharging.

Device is not in test or

connect position.

Rack device to test or connect

position.

Event Alarm button is in OUT

position.

Depress event alarm button.

4

Device status green light

does not go on within 2

minutes after push to charge

button is pressed.

Device is not in test or

connect position.

Rack device into test or

connect position.

5

No system lights illuminate at

start up.

UPS (if so equipped) is not

turned on.

Turn on UPS and allow to

charge for 8 hours.

White light may not be

working properly.

Perform light test by rotating

ACT switch counterclockwise to

TEST position and replace white

light if necessary..

6

System status white light

does not illuminate when

Activation switch is rotated

clockwise.

Arc Vault relay may not be

working properly.

Call GE Engineering field

services at 888-GE4-SERV (888-

434-7378) for support.

Device is not in connect

position.

Rack device into connect

position.

86 lockout relay is tripped

(amber light is illuminated).

Reset the 86 lockout relay.

Device is not ready (device

status green light not

illuminated)

Refer to #4.

7

System status blue light does

not illuminate

Blue light may not be working

properly.

Perform light test by rotating

ACT switch counterclockwise to

TEST position and replace blue

light if necessary.

8

Capacitor status green light

does not illuminate

Arc Vault device control

module failure.

Contact GE Engineering field

services at 888-GE4-SERV (888-

434-7378).