EntelliGuard R Circuit Breaker Retrofill AKD-5 Installation Manual DEH-41547 02/12

Figure 35. Breaker Positioned on Rails

19. Using the hand grips on either side, move or push the circuit breaker into the cassette until it

reaches a positive stop (the rollers on circuit breaker are engaged with the racking cams of the
cassette on both sides). Or, from the front, shove the breaker in as far as it can go.

The circuit breaker is now in the DISCONNECTED position (

Figure 36).

20. Push back both the extended rails of the cassette to the stowed position.
21. If the circuit breaker is ON and the springs are charged, to turn the breaker off, press the OPEN

button on the circuit breaker fascia and ensure the circuit breaker contacts are open.

Figure 36. Breaker Ready for Complete Installation