EntelliGuard R Circuit Breaker Retrofill AKD-5 Installation Manual DEH-41547 02/12
Programmer Secondary Disconnect (Breaker Side—N/A)
Programmer secondary disconnects are not provided on AKD5 legacy LVS breakers. If the customer
chooses to use the advanced features of the EntelliGuard ACB, the control wiring needs to be routed
from the LVS directly to the secondary disconnect landing points on the cassette assembly of the
EntelliGuard ACB cassette. Refer to the tables (
Table 7
and
Table 8
) featuring the two 39-blocks (A and B)
that make up the 78-point secondary-disconnects. Ordering info given here:
Install Position Switch Actuator (Breaker Side)
Legacy Breaker
Kit Number
AK50
10106296G1
AK25
10106269G1
AK25
The position-switch actuator assembly for the AK25 should be mounted on the bottom plate of the
cassette assembly of the AK25 retrofill. The actual actuator assembly consists of two plates, one on the
top (top plate) and one on the bottom of the baseplate. The top plate of the actuator interfaces with the
breaker when it is racked in and the motion of the same is transferred to the bottom plate which
interfaces with the position switch lever on the legacy compartment.
Completing the racking in of the EntelliGuard breaker into the cassette corresponds to the end of stroke
of the position switch system in the compartment for AK25 in AKD-5 LVS.
Figure 50
shows the exploded
view of the AK25 retrofill position-switch actuator (actually a bracket assembly);
Figure 51
displays the
assembly from the bottom.
Figure 50. AKD-5—AK25 Retrofill Breaker, Actuator
for Position Switch Assembly (Exploded View)
Figure 51. AKD-5—AK25 Retrofill Breaker,
Actuator for Position Switch Assembly
(Bottom View)