EntelliGuard R Circuit Breaker Retrofill AKD-5 Installation Manual DEH-41547 02/12

3. With each bullet identified, land the non-bullet side to the corresponding feature on the

EntelliGuard R’s 78-point secondary disconnects. (See

Wiring Diagram for the AK/AKR Retrofill on

Page 44.)

If a wire is too long, cut the wire, crimp a new connector, and install the provided wire markers on the
bullets. Refer to

Wiring Diagram for the AK/AKR Retrofill, Page 44

.

Figure 46. Example Wiring Diagram for AK25 Secondary Disconnects and Photo Example

Below are tables (

Table 7

and

Table 8

) featuring the two 39-blocks (A and B). They make up the 78-point