EntelliGuard R Circuit Breaker Retrofill AKD-5 Installation Manual DEH-41547 02/12

Figure 56. AKD-5—AK50 Neutral Bus Rogowski ASM 10108216

Figure 57. Neutral Bus Rogowski
ASM 10108216 Photo

AKD-5—Neutral Sensor Packaging

It must be ensured that the supply power

to the compartment is turned off/

compartment is de-energized for all the

incoming and outgoing circuits of the LVS

prior to any work being conducted on it.

During the installation and related work on

the equipment, it must be ensured that the

operator is using the prescribed PPE for the

specified tasks.

Ensure only qualified personnel install, operate, service, and maintain all electrical

equipment.

• The Neutral Sensor is constructed using a phase sensor encapsulated appropriately to meet

insulation and durability requirements.

• Lead wires are UL-recognized type 18AWG or larger, rated at 600V.

• Lead wires are 6 feet in length, minimum.

• Lead wires are colored white and black.

• The white wire is connected to the “positive” polarity termination.

• The black wire is connected to the “negative” polarity termination.