GE Industrial Solutions EntelliGuard R AKD-5 User Manual

Page 31

Advertising
background image

30

EntelliGuard R Circuit Breaker Retrofill AKD-5 Installation Manual DEH-41547 02/12

22. Remove the racking tool (

Figure 37

) from the storage location on the cassette front panel by

grabbing the handle.

23. Pull out the torque bar from inside the handle and extend the device.

Figure 37. Racking Tool

24.

Figure 38

shows the racking assembly without breaker inserted.

Figure 38. Racking Assembly Inside Switchgear Compartment (w/no breaker)

25. Take a screwdriver, insert it in the slot or rack-out lock, and turn it clockwise 45° so that the racking

handle shutter, inside and behind the racking hole, moves to the right. (It resembles a vehicle
ignition lock. See

Figure 39

.)