EntelliGuard R Circuit Breaker Retrofill AKD-5 Installation Manual DEH-41547 02/12

Remove Existing Iron Core Neutral CT Assembly

It must be ensured that the supply power

to the compartment is turned off/

compartment is de-energized for all the

incoming and outgoing circuits of the LVS

prior to any work being conducted on it.

During the installation and related work on

the equipment, it must be ensured that the

operator is using the prescribed PPE for the

specified tasks.

Ensure only qualified personnel install, operate, service, and maintain all electrical

equipment.


Figure 53

shows a photo of an existing iron core neutral current transformer.

Figure 53. Iron Core Neutral CT

Neutral CT assembly in Cable/Bus Compartment:

1. Verify that the LVS has been de-energized and the breaker in the compartment being retrofitted

are switched off and removed from the LVS.

2. Open the door on the rear of the compartment to gain access the cable/bus compartment of

the LVS.

The existing neutral CT assemblies are usually mounted vertically on two copper bus bars
placed horizontally.