4. The other wire harness supplied loose with kit shall be

connected to the RELT wire harness to signal the input or

output.

5. The wires in harness are color coded for input

and output. Yellow and red wires are for input to

trip unit.

Black and white wires are for output from trip

unit.

6. If required to use the power supply harness for

control power supply, rout the 2-wire harness in

same way above RELT wire harness.

Figure 18

Figure 19

Wire Colour

Slot in 36 pin

connector

Function

Red

4

Input +

Yellow

2

Input -

Black

30

Output +

White

27

Output -

Table 5