SECTION 2 Installation instructions for “RELT wire harness kit” (Catalogue Number – GTURHA)

For GE type AK, AKT, AKS, AKU, AKJ, AKR, AKRU, AKRT, AKJT, AKW

Low Voltage Power Circuit Breakers.

Installing the RELT wire harness

1. Remove the existing MVT trip unit from breaker by pressing

the lever on side of trip unit mounting plate and gently pull

the trip unit toward yourself as facing the breaker,.

2. Loosen the three screws with screwdriver as shown in

figure 3.

Save the screws, washer and nut for mounting back the

plate later.

3. Rotate the mounting plate from frame, being careful not to

pull on existing wires.

Figure 2

Figure 3

Figure 4