16
SECTION 6 Supplement to GEH-5964
For GE type AKR-75, AKR-100 Low Voltage Power Circuit Breakers.
Following text is in addition to Section 3 of GEH5964
Routing the RELT wire harness
1. Route the RELT wire harness (set of 4 wires) from left of
trip unit mounting plate as shown in figure 24.
2. Secure the wires with wire tie as shown in figure 25 and
apply caution label supplied with kit on both breaker
frame & compartment door.
3. Mount the new Entelliguard
TU on front frame.
4. The other wire harness supplied loose with kit shall be
connected to the RELT wire harness to signal the input or
output.
Figure 24
Figure 25