24

5. The other wire harness supplied loose with kit shall be

connected to the RELT wire harness to signal the input or

output.

7 The wires in harness are color coded for input

and output. Yellow and red wires are for input to

trip unit.

Black and white wires are for output from trip

unit.

10. If required to use the power supply harness for control

power supply, rout the 2-wire harness in same way

above RELT wire harness.

Individual wires in power supply harness are color coded

and numbered. The pins should be inserted at correct

places on backside of 36-pin connector. Refer table 18.

11. Refer Entelliguard

TU Installation manual DEH-

4567 for detailed description of input and output

signal requirements.

g _______

GE Consumer & Industrial

General Electric Company

41 Woodford Ave.

Plainville, CT 06062

DEH-3456 R02 0410

 2009 General Electric Company

Figure 42

Wire Colour

Slot in 36 pin

connector

Function

Red

4

Input +

Yellow

2

Input -

Black

30

Output +

White

27

Output -

Table 16

Figure 41

Wire Colour

Slot in 36 pin

connector

Function

Black

35

24 V DC Supply +

White

36

25 V DC Supply -

Table 18

-

+