5. The other wire harness supplied loose with kit shall be
connected to the RELT wire harness to signal the input or
output.
7 The wires in harness are color coded for input
and output. Yellow and red wires are for input to
trip unit.
Black and white wires are for output from trip
unit.
10. If required to use the power supply harness for control
power supply, rout the 2-wire harness in same way
above RELT wire harness.
Individual wires in power supply harness are color coded
and numbered. The pins should be inserted at correct
places on backside of 36-pin connector. Refer table 18.
11. Refer Entelliguard
TU Installation manual DEH-
4567 for detailed description of input and output
signal requirements.
g _______
GE Consumer & Industrial
General Electric Company
41 Woodford Ave.
Plainville, CT 06062
DEH-3456 R02 0410
2009 General Electric Company
Figure 42
Wire Colour
Slot in 36 pin
connector
Function
Red
4
Input +
Yellow
2
Input -
Black
30
Output +
White
27
Output -
Table 16
Figure 41
Wire Colour
Slot in 36 pin
connector
Function
Black
35
24 V DC Supply +
White
36
25 V DC Supply -
Table 18
-
+