SECTION 8 Supplement to DEH-40008 & DEH-40009

For Allis Chalmers LA-600, LA-800, LA-1600, Blue & Gold version Low Voltage Power

Circuit Breakers.

Following text is in addition to Section 4 of DEH-40008 & DEH-40009

Routing the RELT wire harness

1. Route the RELT wire harness (set of 4 wires) from right of

trip unit mounting plate as shown in figure 30. Secure the

extra length of wire harness by coiling inside steel rail as

shown in figure.

2. Secure the wires harness with wire tie to the frame in a

location where it is accessible in switchgear. Figure 31

shows a suggested location. The actual location is

dependent on the configuration of equipment and may

be determined by field engineer.

Generally this RELT wire harness is routed along with

communication wire harness & tied at the same location

as communication wire harness.

Apply caution label supplied with kit on both breaker

frame & compartment door.

3. Mount the new Entelliguard

TU on front frame.

4. The other wire harness supplied loose with kit shall be

connected to the RELT wire harness to signal the input or

output.

Figure 30

Figure 31

Figure 32