GE Industrial Solutions EntelliGuard TU Conversion kits User Manual

Page 7

Advertising
background image

7

4. Take the “RELT wire harness” (4 wire harness) provided

with kit and insert the pins at the end of wire to respective

terminal on 36-pin connector.

Individual wires in harness are color coded and numbered.

The pins should be inserted at correct places on backside

of 36-pin connector. Refer figure 7 and table 1.

5. The control power supply voltage to trip unit shall be

given through wires 1 and 2 of communication harness

already installed in breaker or supplied.

In case when communication wire harness is not

installed on the breaker, use the power supply harness (2

wire harness) supplied with the kit.

Individual wires in power supply harness are color coded

and numbered. The pins should be inserted at correct

places on backside of 36-pin connector. Refer table 2.

Wire Colour

Slot in 36 pin

connector

Function

Red

4

Input +

Yellow

2

Input -

Black

30

Output +

White

27

Output -

Figure 5

Figure 6

Figure 7

Figure 8

Table 1

Table 2

Wire
Colour

Slot in 36
pin

connect
or

Functio
n

Black

35

24 V DC

+

White

36

24 V DC

-

Advertising