4! modbus exception codes supported – GE Industrial Solutions WattStation Pedestal EVSE Charger MODBUS Register Mapping Guide User Manual

Page 13

Advertising
background image

WattStation

TM

EV Charger MODBUS Register Guide

13 GE Energy ©2012 GE Company All Rights Reserved

The Normal MODBUS function code 23 Response PDU contains the data from the group of registers
that were read. The byte count field specifies the quantity of bytes to follow in the read data field.

MODBUS FC 23 Response (N = Quantity of registers to Read)

Field

Length (bytes)

Value (hex)

Function Code

1

0x17

Read Byte Count

1

2 × N

Read Registers Value

N × 2

Value

Table – 3.11


3.4

MODBUS Exception Codes Supported


In this version architecture design, the MODBUS in EVSE supports the following Exception Codes as
shown in following table.

Exception Code

Exception Code Name

Description

1

Illegal Function Code

The function code received in the MODBUS
request is not an allowable action in EVSE.

2

Illegal Data Address

The data address received in the MODBUS
request is not an allowable address in EVSE.

3

Illegal Data Value

The data address received in the MODBUS
Write request is not an allowable value for
EVSE.

4

Slave Device Failure

An unrecoverable error occurred when the
server (or the slave) was attempting to perform
the requested action.


Table – 3.12


• M

MO

OD

DBBU

USS EExxcceeppttiioonn RReessppoonnssee

Field

Length (bytes)

Value (hex)

Function Code

1

0x80 | Function Code

(or pure addition operation)

Exception Code

2

1-6

Table – 3.13