Evse modbus communication architecture, 1! modbus/tcp communication topologies – GE Industrial Solutions WattStation Pedestal EVSE Charger MODBUS Register Mapping Guide User Manual

Page 7

Advertising
background image

WattStation

TM

EV Charger MODBUS Register Guide

7 GE Energy ©2012 GE Company All Rights Reserved

3

EVSE MODBUS Communication Architecture

3.1

MODBUS/TCP Communication Topologies

EVSE adopts MODBUS/TCP communication acting as a MODBUS/TCP server for integrating with the
building management system. In this architecture, a MODBUS Gateway may be needed to connect
BMS from its field bus network to the Ethernet network as shown in Figure 3.1.

The MODBUS Gateway:

• is implemented as a MODBUS/TCP Client
• identifies the EVSE (MODBUS/TCP server) using EVSE IP address
• maintains the Unit ID of EVSE
• is responsible for corresponding the Unit ID to the EVSE IP address.

Inside the BMS, each EVSE may have a unique unite ID to distinguish each other. The MODBUS Client
devices in the BMS recognize each EVSE with its unit ID for MODBUS communication.

The architecture and design of the MODBUS Gateway and MODBUS/TCP clients are out of the scope
of this specification.


EVSE and BMS MODBUS communication topology architecture
Figure – 3.1

In any deployment environments, MODBUS/TCP client devices can directly communicate with EVSE if
they have the access privileges as shown in Figure 3.2.

EVSE MODBUS/TCP communication topology

Figure – 3.2



MODBUS/TCP

Client



MODBUS/TCP

Server

MODBUS/TCP Request

MODBUS/TCP Response


MODBUS

Client in

BMS


EVSE

(MODBUS/TCP

Server)

MODBUS/TCP Request

MODBUS/TCP Response


MODBUS
Gateway

MODBUS Request

MODBUS Response

Non Ethernet

Ethernet

Advertising