21

6 Battery Connection Panels

Overview

Function

Batteries are connected to the GPS 4827 cabinets on battery connection panels located in the
cabinet directly below or behind the ac input panel. All panels include a battery shunt and an
alarm card that communicates with the controller to provide battery current and status
information. The optional panels may include a low voltage battery disconnect/reconnect
(LVBD/R) contactor. When equipped with a LVBD/R, a contactor control card provides local
manual control of the contactor.

Illustrations

The optional LVBD/R battery connection panel shown in Figures 6-1.

Note: Battery connection panels are blue; dc distribution panels are white.